Measurement and verification framework for a 10 MW steam MVR heat pump
Background
There is no established European standard for the performance rating and field verification of high-temperature industrial heat pumps above 150 °C. Field COP figures reported for industrial heat pumps are often not comparable because system boundaries, measurement points, and uncertainty treatment differ between studies. The case study in MVR4G-DRY project is a rare opportunity to develop and test a rigorous measurement and verification (M&V) protocol on a real system at full industrial scale.
The project is offered by RISE Swedish Research Institute.
Thesis objective
To develop, document, and apply a measurement and verification protocol that allows the thermal and electrical performance of the MVR4G-DRY system to be quantified with stated confidence, and to produce the first verified performance figures for the demonstration.
Sub-objectives:
- Define system boundaries and key performance indicators appropriate to a steam MVR heat pump integrated in a continuous drying process.
- Establish a reproducible data quality and validation procedure.
- Quantify the measurement uncertainty attached to the reported COP and energy savings.
- Identify the instrumentation improvements that would most reduce that uncertainty.
Proposed methodology
- Literature and standards review. ISO 50001 and ISO 50006 on energy performance indicators and baselines, EN 14825 and EN 12900 rating principles, IPMVP option selection, the GUM approach to measurement uncertainty, and IEA HPT Annex reporting practice for industrial heat pumps.
- System and instrumentation mapping. Work through the P&ID, control system tag list, sensor specifications, sampling rates and archiving settings. Produce a measurement point inventory with stated accuracy classes.
- Boundary and KPI definition. Define at least three nested boundaries (compressor train, MVR unit including auxiliaries, and dryer plus MVR as an integrated process) and the corresponding KPIs: COP, seasonal performance factor, specific energy consumption per square metre of board, specific electricity use per tonne of evaporated water, and CO2 intensity using both Swedish grid and marginal emission factors.
- Data quality procedure. Implement automated checks in Python: completeness, range and plausibility limits, frozen and stuck signals, time synchronisation, and closure of energy and mass balances within a stated tolerance. Document the treatment of gaps and outliers.
- Uncertainty analysis. Propagate sensor uncertainties through the KPI expressions using the GUM law of propagation, supported by a Monte Carlo check. Perform a sensitivity study to rank measurement points by their contribution to total uncertainty.
- Application. Apply the protocol to at least one continuous operating period of several weeks, report verified KPIs with confidence intervals, and compare against the design specification.
- Recommendations. Propose instrumentation, logging and procedural changes, and draft the protocol in a form suitable for submission as input to standardisation work.
Expected results
- A documented M&V protocol for high-temperature industrial heat pumps, forming a chapter of Deliverable D4.1.
- A validated measurement point inventory and an implemented data quality toolchain in Python that the project can continue to use.
- First verified COP and energy saving figures for the demonstration with quantified uncertainty, and a design versus measured comparison.
- A ranked list of instrumentation improvements, with the expected uncertainty reduction for each.
- Potential conference paper and a contribution to the HPT Magazine.